UV Steriliser 12 GPM 2 725 L/h stainless steel with timer - Aquapro PR-UV-12GPM-HT1
Part number ART072559 · UV disinfection
Net prices excl. VAT and ordering are reserved for signed-in professional accounts.
Complete UV steriliser set 12 GPM, horizontal
Complete UV steriliser: polished 304 stainless steel treatment chamber, one UV-C lamp, one quartz sleeve and a ballast with timer and audible alarm.
Treatment flow rate 12 GPM, i.e. 2 725 litres per hour. Inlet and outlet 3/4". Horizontal installation.
Aquapro reference PR-UV-12GPM-HT1.
UV-C treatment
Water circulates in the stainless steel chamber around a lamp emitting in ultraviolet C, at 254 nm. This radiation acts on the DNA of micro-organisms present in the water and prevents their multiplication.
The treatment is physical: it adds nothing to the water, does not alter taste, odour or mineral composition, and generates no by-products.
It has, however, no residual effect: the action occurs only in the chamber, during passage. Downstream recontamination is not treated. The steriliser must therefore be placed as close as possible to the point to be protected.
Ballast with timer and audible alarm
The ballast incorporates an operating time counter and a buzzer.
This is a real function, not a gimmick: a UV lamp continues to emit light long after losing its germicidal effectiveness. Radiation at 254 nm decreases with hours, whilst visible blue light remains. Without a counter, nothing indicates that the lamp needs replacing, and the installation runs giving the illusion of functioning.
The timer signals the deadline, the audible alarm makes it impossible to ignore. On an installation in a plant room, this is what triggers the service call at the right time.
Polished 304 stainless steel chamber
Stainless steel withstands pressure, does not degrade under UV radiation and can be cleaned. The polished interior reflects radiation and improves dose distribution in the chamber.
Working pressure 8 bar. Construction in 316 stainless steel is available as an option, for more aggressive waters.
Sizing: flow rate determines everything
A UV steriliser is sized by the maximum flow rate passing through it, not by average flow rate.
Water exposure time to the lamp decreases as flow rate increases. Beyond the nominal flow rate, the dose received drops and treatment loses its effectiveness, with no signal to indicate this.
2 725 L/h corresponds to the entry point of a large individual house or a small tertiary installation. Check the actual peak flow rate of the installation before confirming capacity.
Pre-filtration mandatory upstream
UV radiation does not penetrate particles. Turbid or loaded water creates shadow zones in the chamber, and micro-organisms sheltered behind a particle do not receive the dose.
Pre-filtration is therefore essential, typically 5 microns, more open at first stage on loaded water.
Water must be clear at the steriliser inlet: this is an operating requirement, not a comfort recommendation.
Specifications
- Model: horizontal
- Flow rate: 12 GPM, i.e. 2 725 L/h
- UV power: 40 W
- Inlet / outlet: 3/4"
- Number of lamps: 1
- Number of quartz sleeves: 1
- Ballast: yes, with timer
- Audible alarm: yes
- Working pressure: 8 bar
- Ambient temperature: 2 to 40 °C
- Power supply: 220 V
- Chamber: polished SS 304 stainless steel
- Construction: 304 SS stainless steel, option 316 SS stainless steel
Maintenance
UV lamp: annual replacement, according to hours recorded by the timer. A lit lamp is not an effective lamp.
Quartz sleeve: periodic cleaning. A deposit of scale or iron on the quartz blocks radiation. On hard or ferruginous water, this is the most frequent maintenance point.
O-rings: check at each intervention on the sleeve.
Switch off electrical power and depressurise before any intervention. Do not touch the lamp or quartz with bare hands: fingerprints bake onto the glass and create opaque spots.
Installation
Horizontal in-line installation, after pre-filtration, as close as possible to the point to be protected.
To be provided:
- an isolation valve upstream and downstream
- axial clearance to extract the lamp and sleeve: the unit measures 900 mm, approximately the same clearance is needed along the axis
- an electrical outlet nearby
- an ambient temperature between 2 and 40 °C
- lamp start-up a few minutes before the first draw after shutdown
UV disinfection
- UV ballast / power supply, Aquapro PR-UV-2040BA-T1 ref. ART072560
- UV ballast / power supply, Aquapro PR-UV-6GPM- ref. ART072563
- UV-C steriliser Aquapro 234 W · 72GPM, PR-UV-72GPM-VTM ref. ART072227
- UV-C steriliser Aquapro 195 W · 60GPM, PR-UV-60GPM-VTM ref. ART072226
- UV-C steriliser Aquapro, PR-UV- ref. ART072225
- UV-C steriliser Aquapro 120 W · 36GPM, PR-UV-36GPM-VTM ref. ART072224
- UV-C steriliser Aquapro 80 W · 24GPM, PR-UV-24GPM-VTM ref. ART072223
- UV-C steriliser Aquapro 40 W · 12GPM, PR-UV-12GPM-VTM-S ref. ART072222
- UV ballast / power supply, Aquapro PR-UV-2040BA-36-72GPM ref. ART071805
- UV-C steriliser Aquapro 39 W · 12 GPM, PR-UV-12GPM- ref. ART073460
- UV-C steriliser Aquapro, PR-UV-1GPM- ref. ART073461
- UV-C steriliser Aquapro, PR-UV-1GPM- ref. ART073462
- UV ballast / power supply, Aquapro PR-UV-2040BA-12-24GPM ref. ART073463
- UV ballast / power supply, Aquapro PR-UV-2040BA-M ref. ART073464
- UV-C steriliser Aquapro, PR-UV-6GPM- ref. ART073465
- UV ballast / power supply, Aquapro PR-UV1014-BA-T1 ref. ART073468
- UV-C steriliser Cintropur, CINTRO-FWUV10000 ref. ART074994
- UV-C steriliser Cintropur, CINTRO-FWUV2100 ref. ART074996
- UV-C steriliser Cintropur, CINTRO-FWUVDUO ref. ART074997
- Germicidal UV-C lamp, Cintropur CINTRO-FWUVLAMP2100 ref. ART074999
- Germicidal UV-C lamp, Cintropur CINTRO-FWUVLAMP25 ref. ART075000
- Germicidal UV-C lamp, Cintropur CINTRO-FWUVLAMP95HER ref. ART075001
- Germicidal UV-C lamp, Cintropur CINTRO-FWUVQRTZ2100 ref. ART075002
- Germicidal UV-C lamp, Cintropur CINTRO-FWUVQRTZ25 ref. ART075003
- Germicidal UV-C lamp, Cintropur CINTRO-FWUVQRTZ95 ref. ART075004
- UV-C steriliser Cintropur 25 W, CINTRO-FWUVTRIO ref. ART075006
- Germicidal UV-C lamp, Cintropur CINTRO-FWUVLAMP11 ref. ART075087
- UV-C steriliser Aquapro 12GPM, PR-AQFBB20-TWIN-UV12HT1 ref. ART078136
- UV steriliser part, Aquapro PR-UV-M-SL ref. ART059884
- UV ballast / power supply, Aquapro PR-UV-2040BA-24GPM-HTM ref. ART079130